Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
C-7
2 Specifications
2.2 Power Supply Specifications
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-ADP (4-channel analog Input)
A
Comm
on I
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
-A
D
P
D
FX
3G
-2A
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
-AD
P
G
FX
3G
-1D
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
       
         
   -
A
D
P
J
FX
3U
-4A
D
-P
TW
     
        
      -
A
D
P
2.2
Power Supply Specifications
2.3
Performance Specifications
Item
Specifications
A/D conversion circuit 
driving power
24V DC +20%-15%, 40mA
(It is necessary to connect a 24V DC power supply to the terminal block.)
Interface driving power
5V DC, 15mA
(Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
Item
Specifications
Voltage input
Current input
Analog input 
range
0V to 10V DC
(Input resistance: 194 k
Ω)
4mA to 20mA DC
(Input resistance: 250 
Ω)
Absolute input 
maximum
-0.5V, +15V
-2mA, +30mA
Digital output
12 bits, binary
11 bits, binary
Resolution
2.5mV (10V/4000)
10
μA (16mA/1600)
Total accuracy
±0.5% (±50mV) for 10V full scale
(when ambient temperature is 25
°C ± 5°C)
±1.0% (±100mV) for 10V full scale
(when ambient temperature is 0
°C to 55°C)
±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25
°C ± 5°C)
±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0
°C to 55°C)
A/D conversion 
time
• FX
3U
/ FX
3UC
 Series PLC : 200 
μs (The data will be updated at every scan time.)
• FX
3G
 Series PLC : 250 
μs (The data will be updated at every scan time.)
→ For a detailed description of data update, refer to Section 2.4.
Input
characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 
points occupied
0 point (This number is not related to the maximum number of input/output points of the PLC.)
0
4000
10V 10.2V
4080
Analog input
Digit
al ou
tput
0
1600
20mA 20.4mA
1640
Analog input
Digit
al
 out
pu
t
4mA