4.6 Error Status
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX
3U
-4AD-ADP (4-channel analog Input)
A
Comm
on I
te
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
D
-A
D
P
D
FX
3G
-2A
D
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
A
-AD
P
P
G
FX
3G
-1D
A
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
-
A
D
P
J
FX
3U
-4A
D
D
-P
TW
-
A
A
D
P
4.6
Error Status
If an error is detected in the 4AD-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX
register.
The following table shows the special data registers that store the error status data:
• FX
3U
, FX
3UC
Series PLC
• FX
3G
Series PLC
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.5.
1. Caution regarding use of error status data
If a 4AD-ADP hardware error (b6) or 4AD-ADP communication data error (b7) is detected, it is necessary to
clear the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX
clear the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX
3G
, FX
3U
, FX
3UC
Series PLC
*1.
"1st" for the FX
3G
PLC.
• For FX
3U
, FX
3UC
Series PLC
Special data register
Description
1st
2nd
3rd
4th
D8268
D8278
D8288
D8298
Stores the error status data.
Special data register
Description
1st
2nd
D8288
D8298
Stores the error status data.
Bit
Description
Bit
Description
b0
Channel-1 over-scale detection
b5
Averaging time setting error
b1
Channel-2 over-scale detection
b6
4AD-ADP hardware error
(Power supply error included)
(Power supply error included)
b2
Channel-3 over-scale detection
b7
4AD-ADP communication data error
b3
Channel-4 over-scale detection
b8 to b15
Unused
b4
EEPROM error
-
-
M8002
Error status of 3rd analog special adapter
b6 = OFF (hardware error)
b6 = OFF (hardware error)
Error status of 3rd analog status register
b7 = OFF (communication data error)
b7 = OFF (communication data error)
RST
M6
RST
M7
Initial pulse
MOV
D8288
K4M0
M8000
Normally ON
MOV
D8288
K4M0
*1
*1
M8002
Error status of 1st analog special adapter
b6 = OFF (hardware error)
Error status of 1st analog status register
b7 = OFF (communication data error)
RST
D8268.6
RST
D8268.7
Initial pulse