Mitsubishi Electronics MELSEC-F Manuel D’Utilisation
D-6
2 Specifications
2.1 Generic Specifications
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX
3G
-2AD-BD (2-channel analog Input)
2. Specifications
This chapter describes the general and performance specifications for the 2AD-BD.
2.1
Generic Specifications
*1.
The criterion is shown in IEC61131-2.
*2.
→ For a detailed description of the grounding, refer to Section 3.5.
*3.
If the pressure is higher than the atmospheric pressure, do not use the 2AD-BD.
The 2AD-BD may malfunction.
The 2AD-BD may malfunction.
Item
Specifications
Ambient
temperature
temperature
0 to 55
°C (32 to 131°F) when operating
-25 to 75
°C (-13 to 167°F) when stored
Relative
humidity
humidity
5 to 95%RH (no condensation) when operating
Vibration
resistance
resistance
*1
Frequency
(Hz)
Acceleration
(m/s
2
)
Half amplitude
(mm)
Tests 10 times in each
direction (X-, Y-, and Z-
axis directions) (Total:
80 min, each)
direction (X-, Y-, and Z-
axis directions) (Total:
80 min, each)
DIN Rail Mounting
10 - 57
-
0.035
57 - 150
4.9
-
Direct Mounting
10 to 57
−
0.075
57 to 150
9.8
−
Shock
*1
resistance
147 m/s
2
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
Noise
resistance
resistance
Using noise simulator of:
Noise voltage: 1,000Vp-p / Noise width: 1
Noise voltage: 1,000Vp-p / Noise width: 1
μs / Rise: 1ns / Cycle: 30 to 100Hz
Grounding
Class D grounding (grounding resistance: 100
Ω or less)
<Common grounding with a heavy electrical system is not allowed.>
*2
Working
environment
environment
Free from corrosive or flammable gas and excessive conductive dusts
Working
altitude
altitude
< 2000m
*3
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition