Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
D-14
4 Programming
4.2 List of Special Devices
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3G
-2AD-BD (2-channel analog Input)
4.2
List of Special Devices
If the 2AD-BD is connected, special devices will be assigned automatically as shown in the following table:
R: Read / W: Write
4.3
Switching of Input Mode
Turn the special auxiliary relay on/off to switch the input mode of 2AD-BD between the current input mode
and the voltage input mode.
To switch the input mode, use the following special auxiliary relays:
1. Program Example
To switch the channel input mode, create a sequence program as follows:
Special device
Device number
Description
Attribute Reference
1st board
2nd board
Special auxiliary relay
M8260
M8270
Switches the input mode of channel 1
R/W
Section 4.3
M8261
M8271
Switches the input mode of channel 2
R/W
M8262 to 
M8269
M8272 to 
M8279
Unused (Do not use.)
-
-
Special data register
D8260
D8270
Channel-1 input data
R
Section 4.4
D8261
D8271
Channel-2 input data
R
D8262
D8272
Unused (Do not use.)
-
-
D8263
D8273
D8264
D8274
Averaging time for channel-1 (Setting 
range: 1 to 4095)
R/W
Section 4.5
D8265
D8275
Averaging time for channel-2 (Setting 
range: 1 to 4095)
R/W
D8266
D8276
Unused (Do not use.)
-
-
D8267
D8277
D8268
D8278
Error status
R/W
Section 4.6
D8269
D8279
Model code = 3
R
Section 4.7
Special auxiliary relay
Description
1st board
2nd board
M8260
M8270
Switches the input mode of channel 1 OFF: Voltage input
ON: Current input
M8261
M8271
Switches the input mode of channel 2
1) To switch the input mode of channel
   1 of the 1st analog board to the voltage
    input mode:
M8001
M8260
Normally OFF
2) To switch the input mode of channel 2
     of the 1st analog board to the current 
     input mode:
M8000
M8261
Normally ON