Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
D-17
4 Programming
4.6 Error Status
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3G
-2AD-BD (2-channel analog Input)
A
Comm
on I
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
-A
D
P
D
FX
3G
-2A
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
-AD
P
G
FX
3G
-1D
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
       
         
   -
A
D
P
J
FX
3U
-4A
D
-P
TW
     
        
      -
A
D
P
4.6
Error Status
If an error is detected in the 2AD-BD, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.5.
1. Caution regarding use of error status data
If a 2AD-BD hardware error (b6) or 2AD-BD communication data error (b7) is detected, it is necessary to clear
the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
Special data register
Description
1st board
2nd board
D8268
D8278
Stores the error status data.
Bit
Description
Bit
Description
b0
Channel-1 over-scale detection
b5
Averaging time setting error
b1
Channel-2 over-scale detection
b6
2AD-BD hardware error
b2
Unused
b7
2AD-BD communication data error
b3
Unused
b8 to b15
Unused
b4
EEPROM error
-
-
M8002
Error status of 1st analog board
b6 = OFF (hardware error)
Error status of 1st analog board
b7 = OFF (communication data error)
RST
M6
RST
M7
Initial pulse
FNC 12 
  MOV
D8268
K4M0
M8000
Normally ON
D8268
K4M0
FNC 12 
  MOV