2 Specifications
2.4 Output Mode (Characteristics) BFM #0
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
2.4
Output Mode (Characteristics) BFM #0
For the FX
3U
-4DA, there are two types of output characteristics: voltage (-10 to +10V) and current (0 to
20mA, 4 to 20mA) output characteristics. The output characteristics depend on the set output mode as
described below.
1. Voltage output characteristics [-10 to +10V] (Output mode: 0, 1) 
2. Current output characteristics [0 to 20mA] (Output mode: 2, 4)
3. Current Output characteristics [4 to 20mA] (Output mode: 3)
Set output mode: 0
Output type: Voltage output
Analog output range: -10 to +10V
Digital input range: -32000 to +32000
Offset/gain adjustment: Possible
Set output mode: 1
Output type: Voltage output
(Specification of analog value mV)
Analog output range: -10 to +10V
Digital input range: -10000 to +10000
Offset/gain adjustment: Impossible
Set output mode: 2
Output type: Current output 
Analog output range: 0 to 20mA
Digital input range: 0 to 32000
Offset/gain adjustment: Possible
Set output mode: 4
Output type: Current output
(Specification of analog value 
μA)
Analog output range: 0 to 20 mA
Digital input range: 0 to 20000
Offset/gain adjustment: Impossible
Set output mode: 3
Output type: Current output
Analog output range: 4 to 20mA
Digital input range: 0 to 32000
Offset/gain adjustment: Possible
10
10.2
-10.2
-10
-32000
32000
0
32640
-3
2640
Digital
value
Output voltage (V)
10
10.2
-10.2
-10
-10000
10000
0
10200
-1
0200
Digital
value
Output voltage (V)
20
0
32000
20.4
32640
Digital value
Current
output (mA)
20
0
20000
20.4
20400
Current
output (mA)
Digital value
20
0
32000
20.32
32640
4
Digital value
Current