 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
5.4.19 BFM #61: Error status data automatic transfer-to data register specification
Setting range: 0 to 7999
Initial value: K200
Numeric data type: Decimal (K)
Use this function to automatically transfer the error status data (BFM #29) to the data register specified in
BFM #61.
When an error is detected, data will be automatically transferred from FX
3U
-4DA to the PLC. For this reason,
the PLC does not need a program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the error status (BFM #29), refer to Subsection 5.4.12.
1. If "BFM #61 = K200 (initial value)" 
2. Cautions regarding error status automatic transfer function setting
• If a data is already specified for the other automatic transfer functions, do not specify the same data 
register.
• This function is valid by turning on b0 of the status automatic transfer function setting (BFM #60).
• When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
• The data set in BFM #61 will be retained in the EEPROM.
3. Cautions regarding EEPROM writing
If data is set in BFM #0, #5, #10 to #17, #32 to #35, #50 to #54 or #60 to #63, the data will be written in the
EEPROM of FX
3U
-4DA.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewritable times is 10,000. Therefore, when creating a program, do not
frequently write data in the above buffer memories (BFM).
Specified data 
register
Description
D200
Value of error status (BFM #29)