 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
6.5
Details of table output error
When an error related to the table output function occurs, the error code is stored in BFM #90, and the device
number or the buffer memory that has developed the error is stored in BFM #91.
1. Error code table and details of error source numbers
Error code 
(BFM #90)
Details of error
Table output error source number 
(BFM #91)
K111
The number of patterns in the data table that is held in
the PLC does not meet the following requirement.
≤ Number of patterns ≤ 10
Device number where the number of
patterns is specified (same as the head
device number in the data table)
K121
The number of points in the data table that is held in the
PLC does not meet the following requirement.
≤ Number of patterns ≤ 99
Device number where the number of
patterns is specified
K122
The number of points in the data table that is held in the
buffer memory does not meet the following requirement.
≤ Number of points ≤ 99
Number of BFM where the number of
points is specified
K131
"The condition after output at final point in pattern"
specified in the data table that is held in the PLC is not 0
or 1. 
Device number where "the condition after
the final point output point in pattern" is
specified
K132
"The condition after output at final point in pattern"
specified in the data table that is held in the buffer
memory is not 0 or 1.
Number of BFM where "the condition after
output point in the pattern" is specified
K151
The output update time in the data table that is held in the
PLC does not meet the following requirement.
≤ Output update time ≤ 32767
Device number where the output update
time is specified
K152
The output update time in the data table that is held in the
buffer memory does not meet the following requirement.
≤ Output update time ≤ 32767
Number of BFM where the output update
time is specified
K161
The output update time unit in the data table that is held
in the PLC is not 0, 1, 2 or 3.
Device number where the output update
time unit is specified
K162
The output update time unit in the data table that is held
in the buffer memory is not 0, 1, 2 or 3.
Number of BFM where the output update
time unit is specified
K171
The interpolation method in the data table that is held in
the PLC is not 0, 1 or 2.
Device number where the interpolation
method is specified
K172
The interpolation method in the data table that is held in
the buffer memory is not 0, 1 or 2.
Number of BFM where the interpolation
method is specified
K21
The head device number BFM #98 in the data table to be
transferred is out of the setting range.
K98
K22
The value indicated by b0 to b3 of the transfer command
BFM #99 is not 0 or 1.
K99
K23
The value indicated by b4 to b7 of the source register
type in BFM #99 is not 0 or 1.
K99
K31
Any of the output patterns BFM #81 to #84 does not meet
the following requirement.
≤ Output pattern ≤ 10
One of K81 to K84
K32
The number of table outputs in BFM #85 to #88 does not
meet the following requirement.
≤ Number of repetitions of output ≤ 32767
One of K85 to K88
K33
The bit corresponding to each channel in the table output
start/stop command in BFM #80 is not 0 or 1.
K80