Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
E-53
7 Changing Output Characteristic
7.1 Procedure for Changing Output Characteristics
A
Comm
on I
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
-A
D
P
D
FX
3G
-2A
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
-AD
P
G
FX
3G
-1D
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
       
         
   -
A
D
P
J
FX
3U
-4A
D
-P
TW
     
        
      -
A
D
P
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
7. Changing Output Characteristic
For FX
3U
-4DA, the standard output characteristics are provided for each output mode (BFM #0)at the time of
factory shipment.
Changing the offset data (BFM #10 to #13) and gain data (BFM #14 to #17) can change the output
characteristics of each channel. This chapter describes how to change the output characteristics.
7.1
Procedure for Changing Output Characteristics
1
Cancel the setting change prohibition mode.
If setting change is prohibited, write K3030 in BFM #19. The setting change prohibition mode will
be canceled.
2
Determine the output mode (BFM #0).
Determine the output mode (BFM #0) optimum for the selected channels and the voltage/current
specifications.
Example: Enter "HFF00" in BFM to set output mode 0 for channels 1 and 2 and prevent use chan-
nels 3 and 4 
Cautions regarding data setting
• If a value "1" or "4" is set for a channel, the output characteristics of the channel cannot be changed.
• Set the optimum output mode for the analog signal to be output.
Set value (HEX)
Output mode
Analog output range
Digital input range
0
Voltage output mode
-10V to +10V
-32000 to +32000
1
Voltage output analog value mV
specification mode
The characteristic cannot be changed.
2
Current output mode
0mA to 20mA
0 to 32000
3
Current output mode
4mA to 20mA
0 to 32000
4
Current output analog value 
μA
specification mode
The characteristic cannot be changed.
5 to E
Setting not allowed
-
-
F
Channel not used
-
-