4.6
Error Status
1. Description of setting
If an error is detected on 4DA-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX
3U
, FX
3UC
 Series PLC
• FX
3G 
Series PLC
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
*1.
The 4DA-ADP is supported from June, 2009 and later.
For using the 4DA-ADP, it is necessary to use a main unit whose version supports this function.
For the applicability of each combination of 4DA-ADP and main unit, refer to Section 6.5.
2. Program Example 1 (For FX
3G
, FX
3U
, FX
3UC
 Series PLC)
*2.
"1st" for the FX
3G
 PLC.
Special data register
Description
1st
2nd
3rd
4th
D8268
D8278
D8288
D8298
Stores the error status data.
Special data register
Description
1st
2nd
D8288
D8298
Stores the error status data.
Bit
Description
b0
Channel-1 output data setting error
b1
Channel-2 output data setting error
b2
Channel-3 output data setting error
b3
Channel-4 output data setting error
b4
EEPROM error
b5
Unused
b6
4DA-ADP hardware error (Power supply error included)
*1
b7 to b15
Unused
Y000
M0
Normally
ON
M1
M2
M3
M4
Y001
Y002
Y003
Y004
Channel-1 output data setting error in
Channel-2 output data setting error in
Channel-3 output data setting error in
Channel-4 output data setting error in
EEPROM error in 
the 3rd    adapter
M8000
MOV
D8288
K4M0
3rd    adapter.
*2
3rd    adapter.
*2
3rd    adapter.
*2
3rd    adapter.
*2
*2