2 Specifications
2.2 Performance Specifications
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3G
-1DA-BD (1-channel analog Output)
A
Comm
on I
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
-A
D
P
D
FX
3G
-2A
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
-AD
P
G
FX
3G
-1D
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
       
         
   -
A
D
P
J
FX
3U
-4A
D
-P
TW
     
        
      -
A
D
P
2.2
Performance Specifications
Item
Specifications
Voltage output
Current output
Analog output 
range
0V to 10 V DC
(External load: 2k
Ω to 1MΩ)
4mA to 20mA DC
(External load: 500
Ω or less)
Digital input
12 bits, binary
11 bits, binary
Resolution
2.5mV(10V/4000)
8
μA(16mA/2000)
Total accuracy
±0.5% (±50mV) for 10V full scale
(when ambient temperature is 25
°C±5 °C)
±1.0% (±100mV) for 10V full scale
(when ambient temperature is 0
°C to 55°C)
Shipment adjustment is carried out by external
load resistance 2k
Ω.
If external load resistance becomes larger
than 2k
Ω, the output voltage will increase
slightly.
When the load is 1M
Ω, the output voltage
becomes about 2% higher than the correct
value.
±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25
°C±5°C)
±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0
°C to 55 °C)
D/A conversion 
time
60
μs (The data will be updated at every scan time.)
→ For a detailed description of data update, refer to Section 2.4.
Output
characteristics
Caution:
An area of dead band is located in the region
of 0V. Therefore the output analog value may
not represent the digital value accurately.
Insulation method
• The analog output area is not insulated from the PLC.
Numbers of I/O 
points occupied
0 point (This number is not related to the maximum number of input/output points of the PLC.)
0
10V
4000 4080
Digital input
A
nalog out
put
0
2000
20mA
Digital input
A
n
alog out
put
4mA
2040