Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
A-9
2 Description of Analog Products
2.2 List of Analog Product Models
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
Common Items
A
C
ommon Item
s
B
FX
3U
-4A
D
FX
3UC
-4A
D
C
FX
3U
-4AD
-A
DP
D
FX
3G
-2A
D
-B
D
E
FX
3U
-4D
A
F
FX
3U
-4DA
-A
DP
G
FX
3G
-1D
A
-B
D
H
FX
3U
-3
A-
AD
P
I
FX
3U
-4A
D
-P
T
   
         
       -
A
D
P
J
FX
3U
-4AD
-P
TW
         
         
 -A
D
P
2.2
List of Analog Product Models
The analog input/output products compatible with the FX
3U
/FX
3UC
/FX
3G
 Series PLC are described below:
2.2.1
Expansion board
• FX
3G
 Series PLC
2.2.2
Special adapter
Type
No. of 
channels
Range
Resolution
Function
Refer-
ence
Voltage/current input
FX
3G
-2AD-BD
2ch
Voltage: 0V to 10V DC
2.5mV(12bits) Combined use of voltage and 
current inputs is possible.
D
Current: 4mA to 20mA DC
8
μA(11bits)
Voltage/current output
FX
3G
-1DA-BD
1ch
Voltage: 0V to 10V DC
2.5mV(12bits)
Voltage and current output.
G
Current: 4mA to 20mA DC
8
μA(11bits)
Type
No. of 
channels
Range
Resolution
Function
Refer-
ence
Voltage/current input
FX
3U
-4AD-ADP
4ch
Voltage: 0V to 10V DC
2.5mV(12bits) Combined use of voltage and 
current inputs is possible.
C
Current: 4mA to 20mA DC
10
μA(11bits)
Voltage/current output
FX
3U
-4DA-ADP
4ch
Voltage: 0V to 10V DC
2.5mV(12bits) Combined use of voltage and 
current outputs is possible.
F
Current: 4mA to 20mA DC
4
μA(12bits)
Voltage/current input/output mixture
FX
3U
-3A-ADP
Input
2ch
Voltage: 0V to 10V DC
2.5mV(12bits)
Combined use of voltage/
current inputs and voltage/
current output is possible.
H
Current: 4mA to 20mA DC
5
μA(12bits)
Output
1ch
Voltage: 0V to 10V DC
2.5mV(12bits)
Current: 4mA to 20mA DC
4
μA(12bits)
Temperature sensor input
FX
3U
-4AD-PT-ADP
4ch
Pt100: -50
°C to +250°C
0.1
°C
Compatible with the platinum 
resistance thermometer 
sensor (Pt100).
The product can be switched 
between "Centigrade" and 
"Fahrenheit."
I
FX
3U
-4AD-PTW-ADP
4ch
Pt100: -100
°C to +600°C
0.2
°C to 0.3°C
Compatible with the platinum 
resistance thermometer 
sensor (Pt100).
The product can be switched 
between "Centigrade" and 
"Fahrenheit."
J
FX
3U
-4AD-PNK-ADP
4ch
Pt1000: -50
°C to +250°C
0.1
°C
Compatible with the input 
sensor (Pt1000 and Ni1000).
The product can be switched 
between "Centigrade" and 
"Fahrenheit."
K
Ni1000: -45
°C to +115°C
FX
3U
-4AD-TC-ADP
4ch
Type K: -100
°C to +1000°C 0.4°C
Compatible with 
thermocouple types K and J.
The product can be switched 
between "Centigrade" and 
"Fahrenheit."
L
Type J: -100
°C to +600°C
0.3
°C