4.4
Switching of Output Mode
Turn the special auxiliary relay on/off to switch the output mode of 3A-ADP between the current output mode
and the voltage output mode.
To switch the output mode, use the following special auxiliary relays:
• FX
3U
, FX
3UC
 Series PLC
• FX
3G
 Series PLC
1. Program Example (For FX
3U
, FX
3UC
 Series PLC)
To switch the output mode of a channel, create a sequence program as follows:
4.5
Output Holding Function Cancellation Setting
This setting can hold the analog data output or to output the offset data (0V for voltage output mode, 4mA for
current output mode) when the PLC stops.
To cancel or set the output holding function, use the following special auxiliary relays:
• FX
3U
, FX
3UC
 Series PLC
• FX
3G
 Series PLC
1. Program Example (For FX
3U
, FX
3UC
 Series PLC)
To set or cancel the output holding function for a channel, create a sequence program as follows:
Special auxiliary relay
Description
1st
2nd
3rd
4th
M8262
M8272
M8282
M8292
Switches the output mode
OFF:Voltage output
ON  :Current output
Special auxiliary relay
Description
1st
2nd
M8282
M8292
Switches the output mode
OFF:Voltage output
ON  :Current output
Special auxiliary relay
Description
1st
2nd
3rd
4th
M8266
M8276
M8286
M8296
Cancel output holding 
function setting
OFF: Holds the analog data output 
just before stop of the PLC.
ON :  Outputs the offset data at stop 
of the PLC.
Special auxiliary relay
Description
1st
2nd
M8286
M8296
Cancel output holding 
function setting
OFF: Holds the analog data output 
just before stop of the PLC.
ON :  Outputs the offset data at stop 
of the PLC.
1) To switch the channel output mode of
    channel 1 of the 1st analog special
    adapter to the voltage output mode:
M8001
M8262
Normally OFF
1) To set the output holding function for
    channel 1 of the 1st analog special adapter:
M8001
M8266
Normally OFF