Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
J-18
4 Programming
4.3 Selection of Temperature Unit
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
• FX
3G 
Series PLC
R: Read / W: Write
4.3
Selection of Temperature Unit
To switch the temperature unit of the PTW-ADP turn the special auxiliary relay ON for Fahrenheit (
°F) or OFF
for Centigrade (
°C).
To switch the temperature unit, use the following special auxiliary relays:
• FX
3U
, FX
3UC
 Series PLC
• FX
3G 
Series PLC
1. Program Example (For FX
3U
, FX
3UC
 Series PLC)
Special device
Device number
Description
Attribute
Reference
1st
2nd
Special auxiliary relay
M8280
M8290
Selects the temperature unit.
R/W
Section 4.3
M8281 to 
M8289
M8291 to 
M8299
Unused (Do not use.)
-
-
Special data register
D8280
D8290
Channel-1 temperature 
measurement data
R
Section 4.4
D8281
D8291
Channel-2 temperature 
measurement data
R
D8282
D8292
Channel-3 temperature 
measurement data
R
D8283
D8293
Channel-4 temperature 
measurement data
R
D8284
D8294
Averaging time for channel 1 
(Setting range: 1 to 4095)
R/W
Section 4.5
D8285
D8295
Averaging time for channel 2 
(Setting range: 1 to 4095)
R/W
D8286
D8296
Averaging time for channel 3 
(Setting range: 1 to 4095)
R/W
D8287
D8297
Averaging time for channel 4 
(Setting range: 1 to 4095)
R/W
D8288
D8298
Error status
R/W
Section 4.6
D8289
D8299
Model code = 21
R
Section 4.7
Special auxiliary relay
Description
1st
2nd
3rd
4th
M8260
M8270
M8280
M8290
Selection of temperature unit:
OFF: Centigrade (
°C)
ON: Fahrenheit (
°F)
Special auxiliary relay
Description
1st
2nd
M8280
M8290
Selection of temperature unit:
OFF: Centigrade (
°C)
ON: Fahrenheit (
°F)
1) To switch the temperature unit to centigrade (
°C)
     for the 1st adapter:
M8001
M8260
Normally OFF
2) To switch the temperature unit to Fahrenheit (
°F)
     for the 2nd adapter:
M8000
M8270