Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
K-7
2 Specifications
2.3 Performance Specifications
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
K
FX
3U
-4A
D
-P
NK
          
         
-A
D
P
L
FX
3U
-4AD
-TC
        
        
   -
A
D
P
M
PI
D
 In
st
ru
ctio
n
           (F
N
C
 88
)
2.3
Performance Specifications
Item
Specifications
Centigrade (°C)
Fahrenheit (°F) 
Input signal
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
JIS C 1604-1997
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
DIN 43760-1987
Rated temperature 
range
Pt1000
-50°C to +250°C
Pt1000
-58°F to +482°F
Ni1000
-40°C to +110°C
Ni1000
-40°F to +230°F
Digital output
Pt1000
-500 to +2500
Pt1000
-580 to +4820
Ni1000
-400 to +1100
Ni1000
-400 to +2300
Resolution
Pt1000
0.1°C
Pt1000
0.2°F
Ni1000
Ni1000
Total accuracy
±0.5% for full scale (when ambient temperature is 25°C±5°C)
±1.0% for full scale (when ambient temperature is in the range of 0 to 55°C)
A/D conversion 
time
• FX
3U
/FX
3UC
 Series PLC : 200
μs (The data will be updated at every scan time.)
• FX
3G
 PLC : 250
μs (The data will be updated at every scan time.)
For a detailed description of data update, refer to Section2.4.
Input 
characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 
points occupied
0 points
(This number is not related to the maximum number of input/output points of the PLC.)
0
+250
°C
+2500
-50
°C
-500
Approx.
-55
°C
Approx.
+256
°C
+2560
-550
-Pt1000
0
+110
°C
+1100
-40
°C
-400
Approx.
-45
°C
Approx.
+115
°C
+1150
-450
-Ni1000
0
+4820
-580
+4920
-670
-Pt1000
Approx.
+492.8
°F
+482
-58
Approx.
-67
°F
°F
°F
0
+2300
-400
+2390
-490
-Ni1000
Approx.
+239
°F
+230
°F
-40
°F
Approx.
-49
°F