Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
K-20
4 Programming
4.4 Input sensor selection
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
4.4
Input sensor selection
Turn on the Pt1000 type or off the Ni1000 type selection special auxiliary relay to select the Pt1000 or Ni1000
for PNK-ADP.
The input sensor type will be selected for all the channels at the same time.
To select the input sensor type, use the following special auxiliary relays:
• FX
3U
, FX
3UC
 Series PLC
• FX
3G
 Series PLC
1. Program Example (For FX
3U
, FX
3UC
 Series PLC)
Special auxiliary relay
Description
1st
2nd
3rd
4th
M8261
M8271
M8281
M8291
Input sensor selection:
OFF: Pt1000
ON: Ni1000
Special auxiliary relay
Description
1st
2nd
M8281
M8291
Input sensor selection:
OFF: Pt1000
ON: Ni1000
1) To select Pt1000 for the 1st adapter:
M8001
M8261
Normally OFF
2)To select Ni1000 for the 2nd adapter :
M8000
M8271
Normally ON