Mitsubishi Electronics MELSEC-F Manuel D’Utilisation
A-21
4 Comparison of Performance Specifications
4.1 Analog Input
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
Common Items
A
C
ommon Item
s
B
FX
3U
-4A
D
D
FX
3UC
-4A
D
D
C
FX
3U
-4AD
-A
DP
D
FX
3G
-2A
D
D
-B
D
E
FX
3U
-4D
A
A
F
FX
3U
-4DA
-A
DP
G
FX
3G
-1D
A
A
-B
D
H
FX
3U
-3
A-
AD
P
P
I
FX
3U
-4A
D
D
-P
T
-
A
D
P
J
FX
3U
-4AD
-P
TW
-A
D
P
4. Comparison of Performance Specifications
The analog product performance specifications are shown in the following tables. Select the optimal product
for your equipment.
for your equipment.
4.1
Analog Input
4.1.1
FX
3U
-4AD-ADP
Specifications
FX
3U
-4AD-ADP
Voltage input
Current input
Number of input points
4ch
Analog input range
0V to 10V DC
(Input resistance: 194 k
Ω)
4mA to 20mA DC
(Input resistance: 250
Ω)
Absolute maximum input
-0.5V,+15V
-2mA,+30mA
Offset
Impossible to change
Impossible to change
Gain
Digital output
12 bits, binary
11 bits, binary
Resolution
2.5mV(10V
×1/4000)
10
μA(16mA×1/1600)
Ove
ral
l ac
cura
cy Ambient temperature
:25
±5°C
±0.5%(±50mV) for 10V full scale
±0.5%(±80μA) for 16mA full scale
Ambient temperature
:0 to 55
:0 to 55
°C
±1.0%(±100mV) for 10V full scale
±1.0%(±160μA) for 16mA full scale
Time required for A/D
conversion
conversion
• FX
3U
/FX
3UC
Series PLC : 200
μs (Data updated every scan time.)
• FX
3G
Series PLC : 250
μs (Data updated every scan time.)
Input characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
occupied
occupied
0 point (This number is not related to the maximum I/O points of the PLC.)
0
4000
10V
4080
Analog input
Digital output
10.2V
0
1600
20mA
1640
Analog input
D
ig
ita
l o
u
tp
u
t
4mA
20.
4m
A