Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
L-15
3 Wiring
3.6 Caution Regarding Wiring
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-TC-ADP (4-channel Thermocouple Data Input)
K
FX
3U
-4A
D
-P
NK
          
         
-A
D
P
L
FX
3U
-4AD
-TC
        
        
   -
A
D
P
M
PI
D
 In
st
ru
ctio
n
           (F
N
C
 88
)
3.5.2
Wiring of the thermocouple type J
*1.
To use a J thermocouple type, be sure to connect the thermocouple to these terminals. In addition, 
select J type by turning on the type K/J selection special auxiliary relay.
*2.
Keep the thermocouple away from inductive noise (commercial power, etc.).
3.6
Caution Regarding Wiring
• It is not possible to connect different types of thermocouples to 4 channels of TC-ADP. Be sure to use the 
same type of thermocouple for all the channels.
• TC-ADP is not insulated between the channels. For this reason, be sure to use a non-grounded type 
thermocouple.
• Be sure not to connect to the terminal "
•".
3.7
Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100
Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following 
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
• The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm
2
).
• The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
3k
Ω
ch
TC-ADP
Class-D
grounding
+5V
L +
L -
24+
24-
Terminal block
24V DC
L +, L -, ch :  represents the channel number.
type J
Thermocouple
type J
*2
ch
L +
L -
3k
Ω
Shield
*1
Compensating
lead wire
Temperature
compensating circuit
Temperature
compensating circuit
type J
      
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition