Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
L-20
4 Programming
4.4 Selection of Type K or J
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-TC-ADP (4-channel Thermocouple Data Input)
4.4
Selection of Type K or J
Turn on the J type or off the K type selection special auxiliary relay to select the thermocouple type J or K for 
TC-ADP. 
The thermocouple type will be selected for all the channels at the same time.
To select the thermocouple type, use the following special auxiliary relays:
• FX
3U
, FX
3UC
 Series PLC
• FX
3G
 Series PLC
1. Program Example (For FX
3U
, FX
3UC
 Series PLC)
Special auxiliary relay
Description
1st
2nd
3rd
4th
M8261
M8271
M8281
M8291
Selection of type K or J:
OFF: Type K
ON: Type J
Special auxiliary relay
Description
1st
2nd
M8281
M8291
Selection of type K or J:
OFF: Type K
ON: Type J
2)To select thermocouple type J for the
   2nd adapter :
M8000
M8271
Normally ON
1) To select thermocouple type K for the
    1st adapter:
M8001
M8261
Normally OFF