 PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
M-7
3 Parameter
3.1 Parameter List: (S3) to (S3) + 28
K
FX
3U
-4A
D
-P
NK
          
         
-A
D
P
L
FX
3U
-4AD
-TC
        
        
   -
A
D
P
M
PI
D
 In
st
ru
ctio
n
           (F
N
C
 88
)
3. Parameter
This chapter describes various parameters of PID instruction.
3.1
Parameter List: (S3) to (S3) + 28
Set item
Setting
Remarks
Reference
Sampling time (T
S
)
1 to 32767 (ms)
It cannot be shorter than operation
cycle of the PLC.
Subsection 
3.2.1
+1
Operation
setting (ACT)
bit0
0: Forward operation
1: Backward operation
Operation direction
Subsection 
3.2.2
bit1
0: Input variation alarm is invalid.
1: Input variation alarm is valid.
bit2
0: Output variation alarm is invalid.
1: Output variation alarm is valid.
Do not set to ON bit 2 and bit 5 at
same time.
bit3
Not available
bit4
0: Auto-tuning is not executed.
1: Auto-tuning is executed.
bit5
0: Upper and lower limits of output
value are not valid.
1: Upper and lower limits of output
value are valid.
Do not set to ON bit 2 and bit 5 at
same time.
bit6
0: Step response method
1: Limit cycle method
Select auto-tuning mode.
bit7 to bit15
Not available
+2
Input filter constant (
α)
0 to 99 (%)
When "0" is set, input filter is not
provided.
Subsection 
3.2.3
+3
Proportional gain (K
P
)
1 to 32767 (%)
Subsection 
3.2.4
+4
Integral time (T
I
)
0 to 32767 (
× 100 ms)
When "0" is set, it is handled as "
∞"
(no integration).
Subsection 
3.2.5
+5
Differential gain (K
D
)
0 to 100 (%)
When "0" is set, differential gain is
not provided.
Subsection 
3.2.6
+6
Differential time (T
D
)
0 to 32767 (
× 10 ms)
When "0" is set, differential is not
executed.
Subsection 
3.2.7
+7
   :
+19
These devices are occupied for internal processing of PID operation. Do not change data.