Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
A-24
4 Comparison of Performance Specifications
4.1 Analog Input
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
Common Items
4.1 Analog Input
4.1.4
FX
2N
-4AD
*1.
Adjustment of the offset or gain value will not affect the resolution.
*2.
The offset and the gain should satisfy the following condition:
1V 
 (Gain - Offset) 
 15V
*3.
The offset and the gain should satisfy the following condition:
4mA 
 (Gain - Offset) 
 32mA
Specifications
FX
2N
-4AD
Voltage input
Current input
Number of input points
4ch
Analog input range
-10V to +10V DC
(Input resistance: 200k
Ω)
-20mA to +20mA DC
4mA to 20mA DC
(Input resistance: 250 
Ω)
Absolute maximum input
±15V
±32mA
Offset
-5V to +5V
*1,*2
-20mA to +20mA
*1,*3
Gain
-4V to +15V
*1,*2
-16mA to +32mA
*1,*3
Digital output
With sign, 12 bits, binary
With sign, 11 bits, binary
Resolution
5mV(20V
×1/4000)
*1
20
μA(40mA×1/2000)
*1
Ov
erall a
ccu
ra
cy Ambient temperature:
25
±5°C
-
-
Ambient temperature:
0 to 55
°C
±1.0%(±200mV) for 20V full scale
±1.0%(±400μA) for 40mA full scale
Same accuracy for 4mA to 20mA input
Time required for A/D 
conversion
Normal conversion mode:15ms 
× number of selected channels
High-speed conversion mode: 6ms 
× number of selected channels
Input characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points 
occupied
8 points (Taken from either the input or output points of the PLC.)
0
+2000
+10V
+10.
235
V
+2047
-10V
-10.
240V
-2000
-2048
z
When the input is set from -20 mA to +20 mA:
0
+1000
+20mA
-20mA
-1000
+1600
+32m
A
-1600
-32m
A
z
When the input is set from 4 mA to 20 mA:
0
1000
20mA
4mA
1750
32
m
A