Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
B-17
3 Wiring
3.5 Grounding
A
Comm
on I
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
-A
D
P
D
FX
3G
-2A
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
-AD
P
G
FX
3G
-1D
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
       
         
   -
A
D
P
J
FX
3U
-4A
D
-P
TW
     
        
      -
A
D
P
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD/FX
3UC
-4AD (4-channel Analog Input)
3.4.2
FX
3UC
-4AD
*1.
Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input 
lines from the other motive power lines or inductive lines.
*2.
To use the current input, be sure to short circuit the line between the V  + terminal and the I  
+ terminal (  : channel number).
*3.
The SLD and "
" terminals are connected to each other inside.
*4.
Do not connect any lines to the "
•" terminal.
3.5
Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100
Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following 
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each Series.
• Use the following grounding wire.
• The PLC grounding point should be close, and all grounding wires should be as short as possible.
FX
3U
-4AD
AWG14 (2mm
2
)
FX
3UC
-4AD
AWG22-20 (0.3 to 0.5mm
2
)
250
Ω
6.8k
Ω
ch
200k
Ω
FX
3UC
-4AD
V +, I +, ch   :   represents the channel number.
Terminal
block
I +
COM
V +
*1
I +
COM
V +
250
Ω
6.8k
Ω
ch
200k
Ω
*1
If current input is
selected
If voltage input is
selected
*2
SLD
SLD
*3
*4
Class-D
grounding
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition