Emerson GXT2 3000VA Extended Battery Cabinets GXT2-72VBATT Manuel D’Utilisation

Codes de produits
GXT2-72VBATT
Page de 8
BR
O
-GX
T2@-EN
-XX/C
on
te+Oggioni+P
ar
tne
rs/Prin
ted in It
aly
Technical Data - [Liebert GXT2]
Model GXT2-
GXT2-
GXT2-
GXT2-
GXT2-
GXT2-
GXT2-
700RT230
1000RT230
1500RT230
2000RT230
3KRT230E
4500RT230
6000RT230
Power Rating 
VA
700
1000
1500
2000
3000
4500
6000
W
490
700
1050
1400
2100
3150
4200
Dimensions & Weight
Unit  (WxDxH mm)
87 (2U) x 547 x 430
87 (2U) x 618 x 430
221 (5U) x 547 x 430
Shipping  (WxDxH mm)
268 x 692 x 585
268 x 692 x 585
560 x 690 x 500
Weight - Unit (kg)
22.5
22.6
23.2
24.7
31.9
67
67
Weight - Shipping (kg)
26.5
26.6
27.2
28.7
35.9
76.5
76.5
Input Parameters
Input Voltage and Frequency
220/230/240 VAC user selectable; 40-70Hz
Voltage Range w/o Battery
119-280VAC variable depending on load
176-276VAC
Frequency Range
40-70Hz autosensing
Input Power Connection
IEC320-C14
IEC320-C20
Hardwired
Output Parameters
Output Receptacles
(4) IEC320-C13
(4) IEC320-C13+ 
Hardwired + (2) IEC320-C19
(1) IEC320-C19
Waveform & Frequency
Sinewave; 50 or 60Hz N>ominal (50Hz default) 
Overload warning 
200% for 8 cycles; 130% for10 seconds with transfer to bypass
>200% for 96 milliseconds; 131 - 199%
for 2 seconds;112- 129% for 10 seconds
with transfer to bypass 
Battery Parameters
Type
VRLA, non spillable, flame retardant
Approved manufacturers
China Storage Battery / CSB FR 1270 F2
Panasonic UP-VW1245P1
Yuasa / REW 28-12 FR
Quantity x Voltage x Rating
4 x 12V x 7.0Ah
4 x 12V x 9.0Ah
6 x 12V x 9.0Ah
12 x 12V x 5Ah
Backup Time
Half 
load 
(minutes)
44 25 20 14 16
24
17
Full load (minutes) 
17 
11  
7  
6  
6
10
7
Recharge time
5 hours to 95%
3 hours to 90%
Batteries, other features
Hot Swap Batteries; Deep Discharge Protection; Black Start (w/o mains)
Battery Test
Automatic, User configurable 7-28days
Environmental
Noise
<50dB
<55dB
Operating temp and altitude
0-40°C; 0-3000m
Communications
Serial RS232 standard, USB card, Relay card and SNMP/Web card optional
Common Package
User manual, MultiLink software CD; MultiLink serial cable 3m; Rack mount handles; Tower Support base; Configuration program disk;
Additional Components
(2) 10A IEC320-C13/
+ (1) Schucko CEE 7/7 
Input/output distribution
14 Output Cables
to IEC-320-C19 and  
PD-CEHDWR Input/output
(1) BS1363to IEC-320-C19,
distribution  with maintenance
16A inputpower cord
bypass PD-CEHDWRBYP (optional)
Warranty
2 Years
Standards & Requirements
Safety
EN50091-1-1, CE compliance mark, for both Low Voltage and EMC Directives
EN62040-1-1; TUV/GS, CE EMC Directive
Design, EMI/EMC, 
VFI SS 111 according to IEC6204-3; EN50091-2, Class A; EN61000-4; ISTA Procedure 1A
Transportation
Extended Battery Cabinets
Models
GXT2-48VBATT
GXT2-72VBATT
GXT2-240VBATT
Unit  (WxDxH mm)
87 (2U) x 547 x 430
87 (2U) x 618 x 430
176 (4U) x 522 x 430
Shipping  (WxDxH mm)
268 x 692 x 585
268 x 692 x 585
560 x 690 x 455
Weight - Unit (kg)
28.3
42.5
65
Weight - Shipping (kg)
32.3
46.5
76
Quantity x Voltage x Rating
2 x 4 x 12V x 7.0Ah
2 x 6 x 12V x 9.0Ah
20 x 12V x 9.0Ah
Approved Manufacturers
China Storage Battery / CSBFR 1270 F2
Panasonic/UP-VW1234P1
Yuasa / REW 45-12 FR
Extended Backup time
1 Cabinet (full/half load)
68 / 176
44 / 100
28 / 80
18 / 42
20 / 64
31 / 70
21 / 49
2 Cabinet (full/half load)
136 / 352
88 / 200
56 / 169
42 / 98
40 / 128
54 / 120
38 / 85
3 Cabinet (full/half load)
204 / 528
132 / 300
84 / 240
60 / 140
60 / 192
80 / 164
55 / 123
4 Cabinet (full/half load)
272 / 704
176 / 400
112 / 320
90 / 210
80 / 256
106 / 208
75 / 156
Approximate discharge times are in minutes and at 25°C with resistive load. 
While every precaution has been taken to ensure accuracy and completeness in this brochure, Liebert HIROSS assumes no responsibility, and disclaims all liability for damages resulting from use of
this information or for any errors or omissions. © 2004 Liebert HIROSS. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks
or registered trademarks of their respective owners. 
Liebert HIROSS UPS Headquarters
Via Gioacchino Rossini,6
20098 - S.Giuliano Milanese (MI)
tel.+39 02 982501 fax +39 02 98250337
info.ups@liebert-hiross.com
http://ups.liebert-hiross.com
Liebert HIROSS Services Headquarters
Via Leonardo da Vinci,8
35028 - Piove di Sacco (PD)
tel.+39.049 9719111 fax +39 049 9719257
service@liebert-hiross.com
Emerson Network Power Ltd - UK
Fourth Avenue, Globe Park - Marlow
Buckinghamshire - SL71YG
tel. +44 1628 403200  fax +44 1628 403203
ISO9000
CERTIFIED
COMPANY