LHEDV Series Direct Vent Insert
Liner Installation
The collar extending down from the termination base 
is the air intake connector. Be sure the flex vent, which 
is connected to this collar, is also connected to the 
labelled air intake flue collar on the fireplace. Make sure 
the flex vent is attached on the correct collar and cap 
for exhaust as well.
Slide the insulation provided in the termination kit over 
the two (2) 3" flex liners, (to be attached to the 3" flue 
collar and cap of the termination). Feed one 3" flex 
vent from the bottom of the termination up through the 
4" sleeve. Apply hi-temp sealant on the rain cap col-
lar and slide the flex vent over the end of the rain cap 
collar fastening with the clamp provided. Slide the flex 
liner back down the 4" sleeve until 4" cap slides over 
the sleeve. Attach cap to the sleeve with four (4) screws 
supplied. Apply hi-temp sealant over the air intake 
collar and attach intake flex vent in the same method. 
Feed the two flex liners down the chimney through the 
damper opening. Tighten termination to the chimney 
using the screws provided. (Fig. 10) NOTE: For Round 
Vent Terminations
 - tighten termination to the chimney 
by pushing the four (4) straps of the vent termination 
against the chimney and secure with four (4) screws 
provided. (Fig. 12)
In case the fireplace opening is only minimum height 
21" (533 mm) and access from the front is not possible, 
follow the instructions below. 
1.  Remove flue collar plate assembly. Unbolt the top 
fastener plate and move it to the back first before 
sliding the flue collar plate out from the top of the 
unit. (Fig. 13)
2.  Apply a bead of hi-temp sealant on the end of the 
collar before attaching the liner to the flue collar. 
Fasten it with two clamps then adjust fastener plate 
all the way to the back before sliding flue gas plate 
back onto the unit. (Figs. 14 and 15)
3.  After the flue collar plate is set on the cabinet top, 
make sure the front edge of the flue collar plate is 
completely in contact with the back edge of the cabi-
net top. (Fig. 16)
4.  Put the machine screw back into the fastener plate. 
Bolt the plate until it is locked. (Fig. 17)
Under no circumstances should insulation 
be put between the damper and the top of 
the unit. This may cause condensation and 
overheating of the unit.
FP1280
RHEDV
vent termination
1/03
Flue gas exits 
through the 
vent termination 
rain cap
1) Attach flexible pipe 
to rain cap
2) Secure with clamp
3) Attach raincap to 
vent termiantion us-
ing three screws
Pull flexible pipe 
through vent 
termination
Outside combustion 
air enters through the 
lower level of the vent 
termination
Secure with 
clamp and 
three screws
NOTE:
Minimum Vent Height 
- 12 feet
Maximum Vent Height 
- 35 feet
Air Intake
Exhaust
Air intake collar with 
label secured with 
clamp and three 
screws
Exhaust collar secured 
with clamp and three 
screws
FP1280
Fig. 10  Liner installation.
FP1280a
LHEDV
vent termination
w/zero clearance kit
4/03
6ft.
(183cm)
Spring located in 
between the liner 
and chimney kit
HEDVCAK 
Installation
Secure this 
kit with three 
(3) screws 
provided
HEZC Zero 
Clearance Kit
Air Intake
Exhaust
FP1280a
Fig. 11  Liner installation with zero clearance kit.