Chapter 4: Operation 
45 of 90 
 
4-6  Configuration Settings 
Within the Supervisor Menu the chiller can be configured if options are added in the field.  
These configurations are described below. 
Variable 
Description 
Access Level 
Operator 
Supervisor 
Tank Level Inst 
Activates/Deactivates the tank level control sensor 
 
Auto Water Make-up 
Activates the automatic water makeup valve within 
the controller 
 
Fan Control 
Set to CYCLING when a standard fan starter is used 
to control the fan.  Set to VFD when a variable 
frequency drive is used to control the fan 
 
Disch Press Cntl 
When set to SP, the chiller will control to a static SP.  
When set to AUTO, the chiller will adjust the 
discharge pressure setpoint based on the current 
conditions to increase efficiency. 
 
Sensor Pack Inst 
Activates the optional temperature sensors for 
refrigerant liquid line and suction line temperatures, 
and entering air or water temperature (depending on 
condenser type) 
 
Cond Diff Sw Inst 
Activates the optional water cooled condenser 
differential water pressure switch 
 
Chill Diff Sw Inst 
Activates the optional evaporator differential water 
pressure switch 
 
Clock Board Inst 
Activates the optional controller real time clock card 
 
Heater Installed 
Activates the optional process heater 
 
Analog IN2 
Determines how analog input 2 is used.  It can be set 
to CHIL IN (chiller in temperature), FROM PROC 
(from process temperature), CHIL REM SP (chiller 
remote setpoint) or PROC REM SP (process remote 
setpoint). 
 
Remote SP Mode 
When Analog IN2 is set to REM SP, this determines 
if the LOCAL (entered through the display) setpoint 
or REMOTE (Analog IN2) setpoint is used to 
control the chiller. 
 
Rem SP mA Range 
Determines the signal type (0-20mA or 2-20mA) for 
the Remote Setpoint 
 
Analog In 6 
Determines how analog input 6 is used.  It can be set 
to CHIL IN (chiller in temperature), FROM PROC 
(from process temperature) or TO PROC (to process 
temperature). 
 
Chil Loop Type 
Determines the chiller loop’s type (COOL or 
HEAT/COOL) 
 
Proc Loop Type 
Determines the process loop’s type (COOL, 
HEAT/COOL or HEAT). 
 
Primary Loop 
Determines which loop’s (PROC or CHIL) 
information to display on the first status page of the 
display. 
 
Analog Out 2 
Determines how analog output 2 is used.  It can be 
set to CHIL IN (retransmission of the chiller in 
temperature), CHIL OUT (retransmission of the 
chiller out temperature), FROM PROC 
(retransmission of the from process temperature), 
TO PROC (retransmission of the to process 
temperature) or COOL VLV (process loop cooling 
valve).