Advanced Microprocessor Controls Setup
9
Select Options
The following table lists choices on the Select Options menu. These should match the options installed 
with your unit and should not need to change during normal operation.
Calibrate Sensors
The temperature and humidity sensors can be calibrated by selecting this menu item. “Sensor” shows 
the actual sensor reading or raw reading. “Calibrated” shows the sensor reading after the calibration 
offset has been added. The temperature sensor can be calibrated ±5 degrees Fahrenheit and the 
humidity sensor can be calibrated ±10% RH. When calibrating the humidity sensor, the value shown 
will always be % RH, even though absolute humidity control may be selected. If absolute humidity 
control is selected, the Normal Status Display will display the adjusted reading and may not agree 
with the relative humidity reading displayed while in calibration.
Show DIP Switches
The DIP switch settings can be reviewed from the display panel. Changing the DIP switches requires 
opening the upper panel for access to the DIP switches on the microprocessor control board.
These selections should match options installed on your unit and should not need to change during 
normal operation. Switches 1 through 6 are self-explanatory. Switch 7 is described in more detail 
below. DIP switch 8, not shown above, enables the password feature when set to ON and disables the 
password feature if set to OFF.
Table 3
Select options
Option
Selection
Heating
Yes or No
Humidifier
Yes or No
Dehumidifier
Yes or No
Humidifier Pan
Small or Large
Hot Gas Reheat
Yes or No
Heat Stages*
2 or 3
Dehumidification Stages
1 or 2
*If heat stage is set to 2 on a chilled water unit, the 
reheat 3 output is energized on a call for dehumidification.
NOTE
Power must be cycled off, then on from the unit disconnect switch for the control system 
to update the DIP switch settings (except for switch 8).
Table 4
DIP switch settings
DIP 
Switch 
Number
OFF
ON
1
DX Compressor Cool
Chilled Water
2
Electric/Hot Gas Reheat
Hot Water Reheat
3
2 Step DX
4 Step DX
4
No GLYCOOL
GLYCOOL
5
No Dual Cooling
Dual Cooling
6
Not Used
Not Used
7
Delayed Reheat
Dehumidification with Normal Reheat