HOW TO CHANGE THE SETPOINT 
 
 
 
 
 
 
 
 
HOW TO CHANGE a parameter value 
 
 
 
 
 
 
 
 
 
 
LIST OF PARAMETERS  
Here is a list of the parameters the value of which can be changed in the programming mode, as well as their ranges.  
Display 
Symbol 
Parameter 
Range 
Master-Bilt’s 
BMG/TMG Setting 
SP 
Temperature Set Point 
SPL…SPH 
35°F 
HYS 
Temperature Differential 
1 to 255°F 
5° 
SPL 
Minimum Temperature limit setpoint 
-50…SPH 
27°F 
SPH 
Maximum Temperature limit setpoint 
SPH…120° 
50°F 
AHA 
High Temperature Alarm 
-50…120° 
65°F 
ALA 
Low Temperature Alarm 
50…120° 
0°F 
ATD 
Temperature Alarm Delay 
0…120min 
30min 
DFR 
Number of Defrost Cycle per 24hr 
0…24 
Off Cycle 
DLI 
Defrost Termination Temperature 
-50…120° 
DTO 
Maximum Defrost Duration 
1…120min 
30min 
 
 
 
ELECTRICAL CONNECTIONS 
The  controller  is  provided  with  a  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to  2,5  mm
2
.  Before 
connecting  cables  make  sure  the  power  supply  complies  with  the  control’s  requirements.  Separate  the  probe  cables 
from the power supply cables, the outputs and the power connections. Do not exceed the maximum current allowed on 
each relay, in case of heavier loads use a suitable external relay or contactor’s. 
 
 
PROBE CONNECTIONS  
The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damage  due  to  casual  liquid  infiltration.  It  is 
recommended  to  place  the  thermostat  probe  at  the  warmest  loacation  of  return  air  streams  to  correctly  measure  the 
average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where 
most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.