8. Press RELEASE to automate the chiller start/stop value on the Status01 screen to enable 
the chiller to start. The initial factory setting of this value is overridden to stop in order to 
prevent accidental start-up.
Manual Operation of the Guide Vanes
Manual operation of the guide vanes is helpful to establish a steady motor current for 
calibration of the motor amps value. 
In order to manually operate the guide vanes, it is necessary to override the 
TARGET GUIDE 
VANE POSITION value which is accessed on the Status01 screen. Manual control is indicated 
by the word ‘‘SUPVSR!’’ flashing after the target value position. Manual control is also indicated 
on the default screen on the run status line. 
1. Access the Status01 screen and look at the target guide vane position (
). If the 
compressor is off, the value will read zero. 
2. Move the highlight bar to the 
TARGET GUIDE VANE POSITION line and press the 
SELECT softkey.
Do not permit water or brine that is warmer than 110 F (43 C) to flow through the 
cooler or condenser. Refrigerant overpressure may discharge through the relief 
devices and result in the loss of refrigerant charge.
WARNING
!
WARNING