Carrier 17/19EX Manuel D’Utilisation

Page de 437
LID Default Screen Menu Items 
To perform any of the operations described below, the PIC must be powered up and have 
successfully completed its self test. 
The Default screen menu selection offers four options (Status, Schedule, Setpoint, and 
Service). The Status menu allows for viewing and limited calibration/modification of control 
points and sensors, relays and contacts, and the options board. The Schedule menu allows for 
the viewing and modification of the Local Control, CCN Control, and Ice Build time schedules. 
Numerous set points including Base Demand Limit, LCW, ECW, and Ice Build can be adjusted 
under the Setpoint menu. The Service menu can be used to revise alarm history, control test, 
control algorithm status, equipment configuration, equipment service, time and date, attach to 
network, log out of device, controller identification, and LID configurations. 
 and 
 provide additional information on the menu structure. 
Press the MENU softkey to select from the 4 options. To view or change parameters within 
any menu structure, use the SELECT softkey to choose the desired table or item. The softkey 
modification choices displayed will depend on whether the selected item is a discrete point, 
analog point, or an override point. At this point, press the softkey that corresponds to your 
configuration selection or press the QUIT softkey. If the QUIT softkey is depressed, the 
configuration will not be modified. Use the following softkeys to access and select the desired 
section.