Control circuit specifications
2
*1
Set Pr. 73Pr. 267, and a voltage/current input switch correctly, then input an analog signal in accordance with the setting.
Applying a voltage signal with voltage/current input switch ON (current input is selected) or a current signal with switch OFF (voltage input is
selected) could cause component damage of the inverter or analog circuit of signal output devices. 
*2
Refer to Chapter 4 of  
 
the Instruction Manual (Applied).
(2) Output signals
Fr
eq
ue
ncy
 s
et
tin
g
10E
Frequency 
setting power 
supply
When connecting the frequency setting potentiometer at an initial 
status, connect it to terminal 10.
Change the input specifications of terminal 2 when  connecting it 
to terminal 10E. (Refer to Pr. 73 Analog input selection in Chapter 4 of 
 the Instruction Manual (Applied).)
10VDC
Permissible load 
current 10mA
*2
10
5VDC
Permissible load 
current 10mA
2
Frequency 
setting
(voltage)
Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides the 
maximum output frequency at 5V (10V, 20mA) and makes input 
and output proportional. Use Pr. 73 to switch from among input 0 
to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA.
Set the voltage/current input switch in the ON position to select 
current input (0 to 20mA). 
Voltage input:
Input resistance 
10k
Ω ± 1kΩ 
Maximum 
permissible voltage 
20VDC
Current input:
Input resistance 
245
Ω ± 5Ω 
Maximum 
permissible current 
30mA 
4
Frequency 
setting
(current)
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the 
maximum output frequency at 20mA  makes input and output 
proportional. This input signal is valid only when the AU signal is 
ON (terminal 2 input is invalid). 
Use Pr. 267 to switch from among input 4 to 20mA (initial setting), 
0 to 5VDC, and 0 to 10VDC. 
Set the voltage/current input switch in the OFF position to select 
voltage input (0 to 5V/0 to 10V).
(Refer to Chapter 4 of 
 the Instruction Manual (Applied).) Use Pr. 
858 to switch terminal functions.
1
Frequency 
setting 
auxiliary
Inputting 0 to ±5 VDC or 0 to ±10VDC adds this signal to terminal 
2 or 4 frequency setting signal. Use  Pr. 73 to switch between the 
input 0 to ±5VDC and 0 to ±10VDC (initial setting). 
Use Pr. 868 to switch terminal functions. 
Input resistance 
10k
Ω ± 1kΩ 
Maximum 
permissible voltage 
± 20VDC
5
Frequency 
setting 
common
Common terminal for frequency setting signal (terminal 2, 1 or 4) 
and analog output terminal AM. Do not earth (ground).
--------------------
------
Ty
p
e Terminal
Symbol
Terminal 
Name
Description
Rated 
Specifications
Refer to 
page
Re
la
y
A1,
B1,
C1
Relay output 1 
(alarm output)
1 changeover contact output indicates that the inverter 
protective function has activated and the output stopped.
Fault: No conduction between B and C (conduction between A 
and C)
Normal: Conduction between B and C (No conduction between 
A and C)
Contact capacity: 
230VAC 0.3A 
(Power factor=0.4)
30VDC 0.3A
A2,
B2,
C2
Relay output 2
1 changeover contact output
Ty
p
e Terminal
Symbol
Terminal 
Name
Description
Rated 
Specifications
Refer to 
page
Voltage/current
input switch
2
4
switch1
switch2