Schneider Electric Altivar 12 Manuel D’Utilisation
BBV28581 05/2010
79
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu
(continued)
PId-
PID menu
(continued)
PMP-
Pump sub-menu
(continued)
tOF
T
M Time delay before the auxiliary pump stop
command
command
0 to 999.9 s
2 s
This time is necessary to avoid the effects of transient pressure
fluctuation and thus prevent oscillation (pump starting/stopping)
fluctuation and thus prevent oscillation (pump starting/stopping)
Visible only if
Selecting the operating mode
MdE
above is not set to
nO
.
rOF
T
M Ramp for auxiliary pump stopping
0 to 999.9 s
2 s
Visible only if
Selecting the operating mode
MdE
above is not set to
nO
.
nFd
M Zero flow detection period
nO to 20 min
nO
The value 0 deactivates zero flow detection.
Visible only if PID feedback assignment PIF page 70 is not set to nO.
FFd
T
M Zero flow detection activation threshold
0 to 400 Hz
0 Hz
Below this threshold, if
nFd
> 0 and the auxiliary pump is stopped,
zero flow detection is activated.
Visible only if
Zero flow detection period
nFd
above is not set to
nO
.
LFd
T
M Zero flow detection offset
0 to 400 Hz
0 Hz
Visible only if
Zero flow detection period
nFd
above is not set to
nO
.
T