INSTALLING TRANSITION PIPE AND 
STARTER COLLAR
The transition pipe and starter collar shown in 
Figure 9 are supplied with the fireplace, unattached 
and ready for installation. Remove the starter collar 
and set aside. Slide the transition pipe over the vent 
collar and attach with a minimum of three screws. 
Replace the starter collar over the transition pipe 
and attach using four screws located on the leg 
stands (five used on the model M42E). To install 
B-vent piping, slide the first piece of B-vent over 
the transition pipe and attach with either a mini-
mum of two screws or other means approved by 
the vent manufacturer.
Figure 9 - Installing Transition Pipe and 
Starter Collar
B-Vent Piping
Transition Pipe
Starter Collar
Vent Collar
PRE-INSTALLATION 
PREPARATION
Continued
VENTING INSTALLATION
A B-type venting system must be connected to the 
appliance for venting to the outside of the building.
The following section is provided as a guide to a 
standard B-type vent installation.
Standing codes requirements concerning B-type 
vent  installations  may  vary  within  your  state, 
province or local codes jurisdiction. Therefore, 
it  is  recommended  that  you  check  with  your 
local  building  codes  for  specific  requirements 
or in absence of local codes, follow Section 7.0 
of  the  current  National  Fuel  Gas  Code ANSI 
Z223.1/NFPA 54 and in Canada with CAN/CGA 
B149 for Category I systems using double wall 
B-1 vent pipe.
This gas appliance must be vented to the outdoors 
only and may not be terminated into an attic space 
or into a chimney flue servicing a solid-fuel burn-
ing appliance.
This appliance may be vented through a manufac-
tured chimney system or a masonry chimney using 
a B-vent adapter or a chimney liner system if all 
are listed, inspected and approved by local codes 
and/or building authorities.
The examples shown in Figure 10, page 10 are 
typical  of  most  B-vent  installations  and  codes 
practices.
Example 1:
 Shows the minimum allowable sys-
tem height and lateral offset for a 60° degree or 
greater inclination. Code specifies that offsets at 
60° degrees or greater are considered horizontal 
and must follow the 75% percent rule for lateral 
to total vertical system height. Codes also allows 
only one offset in the total system when at 60° 
degrees or greater. The total vertical height in this 
example represents the minimum height of 8 feet 
and therefore the allowable lateral is 6 feet when 
the 75% percent rule applies. If the lateral length 
must exceed 75% then the system must be sized in 
accordance with the Category I venting tables.
Example 2:
 Shows a multiple offset each at 45° 
degrees of inclination. Multiple offsets are permit-
ted if they do not exceed 45° degrees of inclination. 
The total lengths of the two offsets are not required 
to meet the 75% percent allowable rule.
Example 3:
 Shows a single offset at 45° degrees 
of inclination and therefore the lateral length at 
10 feet of offset does not have to meet the 75% 
percent rule.
In each case the offsets must be supported and 
firestops must be positioned wherever the vent 
must  pass  through  a  sub-floor,  ceiling  joist  or 
an attic overhang. The vent pipe must terminate 
vertically into a listed type vent cap and extend a 
sufficient height through an approved roof flash-
ing, roof jack or a roof thimble. At all points the 
listed clearances must be maintained.
Vent terminations must be located in accordance 
with height and proximity rules of NFPA No. 54 or 
CAN/CGA B149. These rules apply to vents at 12 
in. diameter or less and require a minimum height 
in accordance with the roof pitch and a minimum 
of 8 ft. distance from a vertical wall or obstruction 
(see Figure 11, page 10).
If venting horizontally through a side wall be-
comes necessary, a listed thimble approved for use 
with B-type vent must be used. Check with your 
local codes before venting through a side wall. 
Some codes areas allow the use of existing B-type 
vent systems if the system is at or above the recom-
mended diameter of the flue; in this case 6".