Enviro 828 MH Manuel D’Utilisation

Page de 25
10. VENTING 
VENT TERMINATION CLEARANCES 
A= Clearance above grade, verandah, porch, deck, or 
[balcony (*12 inches (30cm) minimum] 
B= Clearance to window or door that may be opened   [*12 
inches (30cm) minimum] 
C= Clearance to permanently closed window [minimum 12 
inches (30cm) recommended to  prevent condensation on 
window] 
D= Vertical clearance to ventilated soffit located  
above 
the terminal within a horizontal   distance of 2 feet (60cm) 
from the center-line  
of the terminal [24 inches ( 60cm) 
minimum] 
E= Clearance to unventilated soffit [18 inches  
(45cm) 
minimum] 
F= Clearance to outside corner [12 inches minimum] 
G= Clearance to inside corner [ 12 inches minimum] 
H= *Not to be installed above a meter/regulator assembly 
within 3 feet (90cm) horizontally  from the center-line of 
the regulator 
I=  Clearance to service regulator vent outlet [*6 feet   (1.8m) 
minimum] 
J= Clearance to non-mechanical air supply inlet to building or 
the combustion air inlet to any   other appliance [12 
inches (30cm) minimum] 
K= Clearance to a mechanical air supply inlet [*6  
feet 
(1.8m) minimum] 
L= *** Clearance above paved side-walk or paved driveway 
located on public property [*7 feet  
(2.1m) 
minimum] 
M= Clearance under verandah, porch, deck, or balcony [*24 
inches (60cm) minimum **] 
*** A vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves 
     both dwellings ** 
  Only permitted if verandah. Porch, deck, or balcony, is fully open on a minimum of 2 sides beneath the floor 
 
• 
As specified in CGA B149 Installation Codes (1991) Note: Local Codes or Regulations may require different clearances 
 
 
 
 
 
 
 
 
 
 
 
 
 
 