Dell PowerVault 720N, 740N, and 760N Installation and Troubleshooting Guide
A rack mounting kit, consisting of:
— Two rack adapter rails and mounting hardware 
— A 1/2-U filler panel and mounting hardware (including cage nuts and cage nut 
installation tool)
— A cable management clip with mounting hardware
+ /
) 5
Observe the following requirements, cautions, and warnings when you install the filer 
in a rack (the filer ships with front installation brackets installed).
Ensure that the rack mounting holes meet ANSI/EIA-310-D-92 specifications for 
19-inch (483-mm.) wide equipment.
Ensure that equipment installed above the filer is no closer than 0.875-inch 
(22.2-mm) from the top of the filer’s ventilation holes.
; .-(
  %
.-( %   .-(
.-(  
!"# <= %  >?@ AB + C  $
+ '
! 9, DAA 1% '
% / ( +
1   (
9, DAA
( + 
) !%
The left- and right-hand rack adapter rails have six threaded holes on the front and four 
on the back. The multiple holes allow users to install the rack adapter rails in either 
whole-unit or half-unit rack mount positions. The six threaded holes are labeled 1 
through 6 on the front and 7 through 10 on the back, with stamped numbers.
To install the rack adapter rails in a standard 19-inch (483-mm.) equipment rack, per-
form the following steps:
1.
Locate marks on the rack’s left and right front vertical rails. These marks are 
1-U spacing marks that appear every 1.75 inches of vertical rack height (see 
Figure 2-1).