Emerson series dt Manuel D’Utilisation

Page de 16
3 
Level
Installation, operation & maintenance instructions 
IP152, Rev AD 
April 2012 
Mobrey vertical magnetic level controls 
Principle of Operation 
Switching is achieved with the Mobrey  
“three-magnet” system, giving snap-action 
“latch-on” switching. 
Vertical movement of the primary magnet A in a 
glandless pressure tube simultaneously 
actuates magnets B & C to switch the contacts.  
The “three-magnet” system enables the primary 
magnet to pass on and actuate switch 
mechanisms at other levels.  Switch 
mechanisms already actuated can not re-set 
until the return of the primary magnet actuates 
the magnet system once again. 
The primary magnet is moved vertically in the 
pressure tube by a float or displacer 
mechanism which rises and falls with the liquid 
level. 
Identifying your control 
This manual covers the three series of controls: 
B, X and D as shown opposite.  Your control 
has a part number stamped on the nameplate, 
an example of which is shown below.  From this 
number you can identify your control and turn to 
the relevant pages in this manual.  As switch 
mechanisms are common to all three series, 
electrical characteristics are given on page 4. 
Series & material of construction 
Float or displacer module 
Enclosure module 
No. of switch mechanisms 
Type of switch mechanisms 
Chamber or flange module 
Controls manufactured to customer’s 
requirements outside of our standard range will 
be numbered 707
★★
/
★★★
/
 and may be 
identified according to the pictures above. 
Displacer operated controls are covered in 
Installation Instruction booklet IP153. 
Diagrammatic detail of three magnet system 
Series B pages 5 & 6 
XC   13F   S7A   1   D8/112 
Series X pages 5 & 6 
Series D pages 7 & 8