Raypak 181-401 Fascicule

Page de 2
Catalog No.:  2000.203E 
Effective:  12-1-07 
Replaces:  4-1-05
 
Raytherm - Type H   
 
Hydronic Heating Boilers - Indoor 
Model 
           
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Dimensions (Inches) 
Shipping Weight  
(Lbs.) – Approx. 
Model 
No. 
MBTU 
Input 
MBTU 
Output 
AFUE 
 (%) 
Width 
Height 
 
Flue Dia. 
No Pump  w/ Pump
H-181* 181  148  82.6 18-1/4 62-5/8 12-1/16 
191 
221 
H-261 264  216  82.7 22-3/8 
62-7/8 11-1/8 
214 
244 
H-331 
334 274 N/A 
25-3/4 
63-3/4 10-3/4 
234 
264 
H-401* 
399 327 N/A 
29-1/4 65-3/8 12-1/2 
253 
283 
*  Exceptions on H3 (two-stage-fired) models: 
-  Model H3-181 has an 18-1/4” gas connection 
-  Model H3-401 has 375 MBTU Input and 308 MBTU Output 
NOTE: Ratings shown are for elevations up to 2,000 feet. For elevations over 2,000, reduce ratings at the rate of 4% for each  
1,000 feet above sea level. 
 
BOILER RATE OF FLOW AND PRESSURE DROP 
10° 
T 
20° 
T 
30° 
T 
Model 
No. 
GPM 
P FT 
GPM 
P FT 
GPM 
P FT
H-181  30  4.2  N/A N/A N/A N/A 
H-261 43 8.5 22 2.2 N/A N/A 
H-331 N/A N/A  27  3.4  N/A N/A 
H-401 
N/A N/A 33 5.2 22 2.3 
N/A – Not Applicable 
 
 
 
 
Low NOx
Raypak, Inc.  