Emerson XDR Manuel D’Utilisation

Page de 40
Piping
15
Figure 13 Typical Liebert XDR piping—non-interlaced connection
6.3
Connection Methods and Points
Refer to site specific drawings for general locations of the piping connections. For Liebert XDR con-
nection locations, refer also to Figures 1417 and 21.
The assembly and connection means used for piping in the Liebert XD system are the same as those 
used in conventional refrigeration systems. Observe all standard practices during installation and 
startup to prevent damage and contamination. All piping must be ASTM Type ACR copper.
The Liebert XDR has supply and return piping access on the top of each module. Supply piping con-
nection is 1/2" OD copper pipe, and return piping connection is 7/8" OD copper. The hard-piped Lie-
bert XDR has a low-pressure nitrogen holding charge. 
Both supply and return couplings may be supplied with optional one-shot couplings. These couplings 
contain pressurized R-134a refrigerant inside the Liebert XDR.
For Liebert XDRs with removable couplings, the supply piping connection is 1/2" OD and the return 
piping connection is 7/8" OD. Both the Liebert XDR and the Liebert XD Flex Pipe with removable cou-
plings have a low-pressure nitrogen holding charge.
6.4
Insulation
To minimize the possibility of condensation, insulate all piping between the Liebert XDR and the Lie-
bert XDP or Liebert XDC.
6.5
Venting the Holding Charge for Hard-Piped or Removable Liebert XD Flex Pipe 
Couplings
The Liebert XDR in either hard-piped configuration or with removable couplings is shipped with a 
low-pressure holding charge (about 30 psi) of nitrogen to prevent oxidation and moisture. This must be 
vented from the refrigeration circuit before removing the copper cap.
To vent the holding charge:
1. Find the Schrader valve that retains the nitrogen holding charge in the Liebert XDR. The valve is 
inside the rear door, on the supply line (see Figure 14 for hard-piped connections and Figure 22 
for removable couplings).
2. Vent the holding charge in the circuit by depressing the pin in the Schrader valve on the supply 
line.
3. Replace and secure the cap on the Schrader valve that was opened.
NOTE
This procedure is for modules with hard-piped or removable couplings ONLY. Do not vent a 
pre-charged Liebert XDR or pre-charged Liebert XD Flex Piping.
TOP VIEW
Return
Supply
Liebert XDP/
Liebert XDC A
Liebert XDR A Liebert XDR A Liebert XDR A Liebert XDR A
DRAWING IS 
NOT TO SCALE