Hussmann proto-aire Manuel De Montage

Page de 124
Protocol™ Installation and 
Service Manual 
Step A9 
At this point, it is assumed that the electronic control board is in switchback 
(see page 6-6 for details describing switchback).  If the compressor you are 
trying to turn ON is not wired to the switchback control circuit (refer to the 
supplied customized wiring diagram), you will need to investigate the cause 
of this switchback condition and correct the existing problem. 
 
Step A10 
If the compressor you are trying to turn ON is wired into the switchback 
control circuit, use a digital voltmeter and determine where the circuit is 
being broken.  The switchback control circuit originates from the phase 
monitor, passes through the switchback relay on the control board, through 
the low pressure mechanical backup switch, then back through the control 
board relay and fuse, through the high pressure safety switch, the discharge 
line thermostat and finally through the electronic oil level control safety. 
 
Problem B:  Evaporator is not defrosting. 
 
Step B1 
Visually observe if the Alarm Relay LED on the control board is ON.  If 
LED is ON, got to step B2.  If LED is OFF, refer to the Troubleshooting 
Alarms
 section of this document. 
 
Step B2 
Verify that the Clock contained in the Protocol is keeping time.  Access and 
select the Set the Clock submenu.  If the clock is running, go to step B3.  If 
the clock is not running, try changing the time to the correct setting.  You 
may want to consult the section on Electrical Noise contained within this 
manual. 
 
Step B3 
Enter the defrost circuit number you wish to turn ON and activate it.  Now 
exit and go to the Defrost Menu.  Observe the circuit you forced into 
defrost.  If the status indicates defrost proceed to Step B4.  If the status does 
not indicate defrost, go to Step B7. 
 
Step B4 
Visually observe which defrost relay located on the defrost board is 
energized.  The corresponding indicator light on the defrost board should be 
ON.  If the indicator light is ON, proceed to Step B5.  If the indicator light is 
OFF, proceed to Step B10. 
 
Step B5 
At this point, we have assumed that the control is responding correctly and 
the problem lies within the control panel.  Use a digital voltmeter to check 
that voltage is present at the correct terminal blocks in the power 
distribution box.  You will need to refer to the supplied customized wiring 
diagram to determine which terminal blocks are providing power for the 
particular case load you are defrosting.   If voltage is present at the terminal 
blocks, verify that the case is in defrost by visual inspection and then return 
to Step B6.  If voltage is not present at the terminal blocks, go to Step B11. 
 
 
Step B6 
If the status of this defrost circuit indicates it is deactivated, reactivate the 
circuit and verify the programming of this circuit as outlined in controller 
manual.  If the status of this defrost circuit indicates that it is not installed, 
 
110