Hussmann proto-aire Manuel De Montage

Page de 124
Protocol™ Installation and 
Service Manual 
 
Sample
 Protocol™ Checklist 
Store: Joe’s Market 
 
 
Location:  Anytown, USA 
Date:  6/7/2004 
 
 
Time:   
Unit 
Model Number 
PH06PK-MEMEMEMEMEMF 
Serial Number 
 
Factory Order Number 
06542 
Manufacture Date 
08/31/98 
Defrost 
 
Circuit 
NO. 
1 2  3 
4 5  6 
7  8 
Type 
Off Off  Off 
Off Off  Off 
 
 
No./Day 
4 3  3 
2 1  3 
 
 
Length 
40m 45m  45m 
45m 60m  45m 
 
 
Superheat 
42° 
Suction Set Point 
52 psig 
Suction Pressure 
52.0 psig / 17°F Saturated 
Suction Temperature 
59 ° 
Split/Satellite Superheat 
 
Suction Set Point 
 
Suction Pressure 
 
Suction Temperature 
 
Oil 
POE 
Turba-Shed Between 
Glasses 
Pressure Differential 
 
Condenser 
 
Head Pressure 
214.9 psig 
Water Temperature In 
OK 
Water Temperature Out 
OK 
Refrigerant 
404a 
Receiver Level 
 
Liquid Sight Glass 
Foamy 
Compressor No. 
1 2 3 4 5 6 
Model No. 
ZF13K4 
ZH13K2 
ZH13K2 ZH13K2 ZF13K4 ZF15K4 
Discharge 
Temperature 
173 166 166 165 162 165 
Amp 
Draw 
10.2 10.7 10.8 11.2 10.2 12.5 
Shell Temp at Oil Connect  hot 
hot 
warm 
warm 
warm 
warm 
Float or Oil Connect 
¾ 
full 
7/8 
3/4 
1/2 
full 
Oil Control Magnet Cond.   
 
 
 
 
 
Controller 
 
Alarms  
Time & Date Displayed 
 
Notes:  L.L. Filter changed 
All valves adjusted. 4 PEXH4s, 2 C-store Reach Ins, 1 ND5 would not adjust 
Removed T-stats from PEXH4s, ND5s, and DM. 
Raised suction S.P. from 48 psig to 52 psig.  All PEXH4s cleaned.  1-2 inches of slime grew there 
 
118