Protocol™ Installation and 
Service Manual 
Presetting the Degree of Closure 
Look up flow rate (GPM) for each Protocol™.  Find the closest GPM in Table 1. Log the 
listed °Closure Value for each Protocol™ in the Table 1 Value row
 
Establish Length of Run for each Protocol™.  Find the closest Length of Run in Table 2.  
Log the listed °Closure Value for each Protocol™ in the Table 2 value row
 
Add the two values logged for each Protocol™. 
 
Locate the lowest Total.  Subtract it from each Protocol™ Unit’s Total, to get Presetting 
°Closure. 
 
Important Note:  Length of Run includes both the supply and return piping. 
 
Example 
Protocol™ 
A B C D E  F  G H I   
 
Table 1 Value 
(+) 
11 9 14 12 15 7 15 11 8 
 
 
Table 
Value  9 14 5  8 11 9 10 12 18 
 
 
Total 
(-) 
20 23 19 20 26 16 
25 23 26 
 
 
Lowest Total 
16 16 16 16 16 16 16 16 16  
 
Presetting 
°Closure 
4 7 3 4 10 0 9 7 10 
 
 
 
Protocol™ 
 
 
 
 
 
 
 
 
 
 
 
Table 1 Value 
(+) 
 
 
 
 
 
 
 
 
 
 
 
Table 2 Value 
 
 
 
 
 
 
 
 
 
 
 
Total 
(-) 
 
 
 
 
 
 
 
 
 
 
 
Lowest Total 
 
 
 
 
 
 
 
 
 
 
 
Presetting 
°Closure 
 
 
 
 
 
 
 
 
 
 
 
 
 