This range is manufactured with the neutral terminal 
connected to the cabinet. Use a 3-wire UL listed, 40- or 50-
amp power supply cord (pigtail) (see Range Rating chart 
below). If local codes do not permit ground through the 
neutral, use a 4-wire power supply cord rated at 250 volts, 
40 or 50 amps and investigated for use with ranges.
*The NEC calculated load is less than the total connected load 
listed on the model/serial rating plate.
**If connecting to a 50-amp circuit, use a 50-amp rated cord with 
kit. For 50-amp rated cord kits, use kits that specify use with a 
nominal 1
³⁄₈" (34.93 mm) diameter connection opening.
A time-delay fuse or circuit breaker is recommended.
The range can be connected directly to the fused disconnect 
(or circuit breaker box) through flexible or nonmetallic 
sheathed, copper or aluminum cable. See “Electrical 
Connection.”
Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that 
the range can be moved if servicing is ever necessary.
A UL listed conduit connector must be provided at each end 
of the power supply cable (at the range and at the junction 
box).
Wire sizes and connections must conform with the rating of 
the range (40 amps).
The wiring diagram is located on the underside of the storage 
drawer or below the warming drawer in a clear plastic bag.
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the 
cabinet. The ground must be revised so the green ground wire of 
the 4-wire power supply cord is connected to the cabinet. See 
“Electrical Connection.”
Grounding through the neutral conductor is prohibited for new 
branch-circuit installations (1996 NEC); mobile homes; and 
recreational vehicles, or an area where local codes prohibit 
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a 
matching UL listed, 4-wire, 250 volt, 40-amp, range power supply 
cord (pigtail) must be used. This cord contains 4 copper 
conductors with ring terminals or open-end spade terminals with 
upturned ends, terminating in a NEMA Type 14-50R plug on the 
supply end. 
The fourth (grounding) conductor must be identified by a green or 
green/yellow cover and the neutral conductor by a white cover. 
Cord should be Type SRD or SRDT with a UL listed strain relief 
and be at least 4 ft (1.22 m) long.  
The minimum conductor sized for the copper 4-wire power 
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 
250 volt, 40- or 50-amp range power supply cord (pigtail). This 
cord contains 3 copper conductors with ring terminals or open-
end spade terminals with upturned ends, terminating in a NEMA 
Type 10-50P plug on the supply end. Connectors on the 
appliance end must be provided at the point the power supply 
cord enters the appliance. This uses a 3-wire receptacle of NEMA 
Type 10-50R.
Electrical Requirements - Canada Only
If codes permit and a separate ground wire is used, it is 
recommended that a qualified electrical installer determine that 
the ground path is adequate and wire gauge are in accordance 
with local codes.
Be sure that the electrical connection and wire size are adequate 
and in conformance with CSA Standard C22.1, Canadian 
Electrical Code, Part 1 - latest edition, and all local codes and 
ordinances.
A copy of the above code standards can be obtained from:
Canadian Standards Association
178 Rexdale Blvd.
Toronto, ON M9W 1R3 CANADA.
Range Rating*
Specified Rating of 
Power Supply Cord Kit 
and Circuit Protection
120/240 Volts
120/208 Volts
Amps
8.8 - 16.5 KW
16.6 - 22.5 KW
7.8 - 12.5 KW
12.6 - 18.5 KW
40 or 50**
50
4-wire receptacle (14-50R)
3-wire receptacle (10-50R)
WARNING
Electrical Shock Hazard
Electrically ground range.
Failure to do so can result in death, fire, or 
electrical shock.