TOA a-9060dh Mode D'Emploi

Page de 138
99
[Pulse trigger]
Use this method to activate operations for which no definite end can be defined, such as "VOL UP/DOWN"
(Volume Up/Down), "LOADBANK" (Scene memory recall), and "CH ON." Minimum pulse width is 100 ms.
14.1.4. Operation by control input
High
Low
Over 100 ms
State changes at the falling edge. 
[Level trigger]
Use this method to activate "CH MUTE" (Channel mute), "POWER" (Power ON/OFF remote function), "EMG-
MUTE" (Cut-off by emergency control), paging broadcasts, and other operations of which start and end must
be defined.
High
Low
Activated only for this duration
Start
End
For "CH MUTE," "POWER," and "EMG-MUTE" functions, if operated at the front panel (EMG-MUTE does not
accept this access from the front panel) or if other control input to which the same function is assigned is fed,
their states are changed by subsequent panel operations or control input activations. The following example
shows the change in operation when POWER (Power ON/OFF remote function) is assigned to Control inputs
1 and 2;
Control input 1
Control input 2
Unit operation
Power ON
Control input 1 will still keep the power ON after Control input 2 turns the power OFF, however the unit's
power is OFF.