Installation and Operation Manual 
Installation
Mounting Recommendations
The PM2X SPD should be nipple mounted directly to the equipment being 
addressed. The measured torque for tightening the lock nut is not to exceed 
100 in-lbs. Always use the mounting brackets (provided) as primary support.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe 
electrical work practices. See NFPA 70E.
• This equipment must only be installed and serviced by qualified 
electrical personnel.
• Turn off
 
all power supplying this equipment before working on or inside 
equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this 
equipment.
• This equipment must be effectively grounded per all applicable codes. 
Use an equipment-grounding conductor to connect this equipment to 
the power system ground.
Failure to follow these instructions will result in death or serious injury.