APC SurgeArrest PM 208/120V 80KA, Non-modular PMF2X-A Manuel D’Utilisation
Codes de produits
PMF2X-A
Installation and Operation Manual
17
Remote Monitor Option
The option has two LEDs, one red and one green, and an audible alarm with
an enable/disable switch. Normal status is a lit green LED, and no audible
alarm. To test the integrity of the remote monitor, press the push-to-test
switch. The green LED will turn off, the red LED will turn on, and the alarm
will sound, if the alarm is enabled. Releasing the switch will complete the
test; the red LED will turn off, the green LED will turn on and the alarm will
shut off.
an enable/disable switch. Normal status is a lit green LED, and no audible
alarm. To test the integrity of the remote monitor, press the push-to-test
switch. The green LED will turn off, the red LED will turn on, and the alarm
will sound, if the alarm is enabled. Releasing the switch will complete the
test; the red LED will turn off, the green LED will turn on and the alarm will
shut off.
If protection on any phase is lost, the green LED will turn off, the red LED
will illuminate and an alarm will sound. The audible alarm can be silenced by
pushing the alarm enable/disable/test switch. The alarm will silence and the
green alarm LED will not be lit. The red LED will continue to be illuminated
until the inoperative condition has been cleared.
will illuminate and an alarm will sound. The audible alarm can be silenced by
pushing the alarm enable/disable/test switch. The alarm will silence and the
green alarm LED will not be lit. The red LED will continue to be illuminated
until the inoperative condition has been cleared.
The remote monitor includes a 120 Vac to 12 Vdc adapter with a six-foot
power cord. Connections are made to the PM2X SPD diagnostic panel with
the 24-inch dry contact leads (provided). To extend the remote monitor
further (up to 1,000 ft. [305 m]), use an additional length of solid or stranded
30 to 14 AWG wire (not provided).
power cord. Connections are made to the PM2X SPD diagnostic panel with
the 24-inch dry contact leads (provided). To extend the remote monitor
further (up to 1,000 ft. [305 m]), use an additional length of solid or stranded
30 to 14 AWG wire (not provided).
Figure 7:
Remote Monitor Option
= OK
= Fault / Falla / Défaut
Bouton pousser pour vérifier
Monitor Remoto / Moniteur À Distance
[63.5]
2.500
[31.8]
1.25
[88.9]
3.500
[100.3]
3.950
[5.86]
0.230
[5.86]
0.460
[4.75]
2x Ø 0.187
[111.76]
4.400
[3.3]
0.130
[28.58]
1.125
Dry Contacts
120 V power cord
Operation