APC SurgeArrest PM 208/120V 80KA, Non-modular PMF2X-A Manuel D’Utilisation

Codes de produits
PMF2X-A
Page de 20
8
Installation and Operation Manual 
Electrical
Voltage Rating
Prior to mounting the SPD, verify that the device has the same voltage 
rating as the power distribution system in which it is installed. Compare the 
nameplate voltage or model number on the SPD with the nameplate of the 
electrical distribution equipment.
The specifier or user of the device should be familiar with the configuration 
and arrangement of the power distribution system in which the SPD is to be 
installed. The system configuration of any power distribution system is 
based strictly on how the secondary windings of the transformer supplying 
the service entrance main or load are configured. This includes whether or 
not the transformer windings are referenced to earth via a grounding 
conductor. The system configuration is not based on how any specific load 
or equipment is connected to a particular power distribution system. See
 
Table 2 for the service voltage of each SPD.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Confirm the SPD voltage rating on the module or nameplate label is the 
same as the operating voltage.
Failure to follow these instructions will result in death or serious injury.
Table 2:
APC Hardwired SPD Voltage Ratings / Model Numbers
Service Voltage
Peak Surge Current 
Rating Per Phase
Model Number
120/240, 
1 phase, 3 wire
80 kA
PMP2X-A
120/208Y, 127/220Y
3 phase, 3–4 wire
80 kA
PMF2X-A
277/480Y, 
3 phase, 3–4 wire
80 kA
PMG2X-A
220/380Y, 230/400Y, 240/415Y,
3 phase, 3–4 wire
80 kA
PMH2X-A
Electrical