HP AT519A Manuel D’Utilisation

Page de 15
Power Requirements
110-240VAC, 4 wire
Data acquisition board can be powered in parallel or separately.
Sensed Data
HP EIO software will provide the following data points:
Current per circuit with breaker capacity and warning status
Power Factor per circuit
Voltage per phase
Power per circuit, per phase, and total with warning status
Accuracy
*
Current (amperage): +/-2%
Voltage (volts): +/-2%
Power (kw): +/-3%
Installation
Local licensed electrician required for installation and 
*
onsite calibration
HP Energy Meter
HP Energy Meter
HP Energy Meter
HP Energy Meter
Components
Includes HP wireless base station, SquareD ION6200 in single HDM
enclosure, and 3 Split Core CT's, both UL and CE rated
Mounting and Installation HDM Dimensions: 11.92"x7.5"x7.88"
Wall mount ION6200 enclosure. Voltage and CT connections are routed
from source to HDM enclosure.
Power Requirements
110-480VAC
*
, 50/60Hz, up to 2400amps per circuit
*
, 3 or 4 wire, Wye or
Delta.
* Depending on model ordered
Sensed Data
HP EIO software will provide the following data points:
Current per phase (Wye only)
Power Factor per phase (Wye only)
Voltage per phase (Wye L-N and Delta L-L)
Total Power
Average Power (period = 5min sampling interval)
THD
Accuracy
*
Current (amperage): +/-1%
Voltage (volts): +/-1%
Power (kw): +/-2%
Installation
Local licensed electrician required for installation and 
*
onsite calibration
HP Chilled Water Energy
HP Chilled Water Energy
HP Chilled Water Energy
HP Chilled Water Energy
Meter
Meter
Meter
Meter
Components
Includes HP wireless base station, Ultrasonic Flow Meter with remote
transducers, and 2 pipe temperature RTD's
Mounting and Installation Ultrasonic transducers are clamped directly to the chilled water pipe surface.
Pipe temperature RTD's are clamped directly to the chilled water pipe
surfaces.
Control box and wireless node mounted remotely.
Power Requirements
110-240VAC, 50/60Hz
Sensed Data
HP EIO software will provide the following data points:
Supply Volumetric Flow Rate
Supply Temperature
Return Temperature
Accumulated Energy
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental Observer
Environmental Observer
Environmental Observer
Technical Specifications
DA - 13392   Worldwide — Version 2 — November 16, 2009
Page 14