Zigor RHIN PLUS 6KVA 18632 Fascicule

Codes de produits
18632
Page de 2
Specifications may be changed without notice
TECHNICAL SPECIFICATIONS
Rhin Plus series
Power kVA 
10
General
Technology 
Digital On-Line, double conversion, parallel 
Overload 
Inverter supply: up to 150% for up to 160 sec depending on load
Bypass supply: up to 200% for up to 500sec depending on load
Input 
Acceptable Input voltage range
(single phase) 
160~280 Vac
Acceptable frequency 
45~65Hz
Phase / Wire 
Single line + neutral+ ground
Power factor 
Up to 0.99 at 100% linear load
Current THD (100% linear load) 
<6% (100% linear load)
Output
Power (Va/W) 
 
6000/4200 
10000/7000
Voltage (normal mode) 
200/208/230/240Vac (selectable (208/120Vac optional))
Output frequency 
±1Hz±3Hz
Output type 
Screw terminals - for hard wiring facility
Wave form 
Sinewave, total harmonic distortion <3% (no load to full load)
Efficiency AC to AC 
Up to 90% (normal), (ECO: up to 95%)
Crest factor 
3:1
Batteries & Autonomy
Standard battery 
Pb VRLA Sealed lead acid maintenance free
Autonomy (full load) 
8 min  (External Battery Pack)    
5 min  (External Battery Pack)
Charge time 
4 hours to 90%
Capacity 
12V/7Ah 
12V/9Ah
Voltage 
240Vdc
Model BBC20J0007  (018609)
7AH / 80pcs / 18/Kgs (w/o batteries) / 68.0/Kgs / 440x132x680 mm
Model BBC20N0009 (018610)
9AH / 80pcs / 18/Kgs (w/o batteries) / 68.0/Kgs / 440x132x680 mm
Controls 
LEDs & Acoustics 
Line failure, System fault conditions, Overload, Low battery, Transfer to by-pass
Communication
Standard interface RS232 
Input/output voltage Frequency / Temperature / Charge level Battery level 
SNMP  Internal card (optional) 
Historic events/ System analysis
Input/Output connection 
Hardwire facility
External battery connection 
Plug & play
Communication slots 
2nd RS232,USB,RS485, Relay contact, SNMP/WEB Card, etc (optional)
Protection
Current limitation 
Yes
Static by-pass/ manual 
Yes / optional
RFI filter 
Yes
Frequency 
45~65Hz
PFC: Power factor corrector
Battery charger protector 
Yes
Display
On LCD+LED: Line mode,back-up,ECO mode,Bypass supply, Battery low/bad/disconnect, Overload Transfering 
with interruption and UPS fault 
On LCD: Input voltage/frequency, output voltage/frequency, load percentage, battery voltage & inner temperature
Self diagnostics 
Upon Power-on, Front panel setting & software control, 24 hour routine checking
CE Certificates
Norms/Certificates 
ISO Certificate , EN 62040-1-1:2003, UL1778, EN 62040-2, EN 61000-3-2, EN 61000-3-3, FCC class A, CE, cUL, UL
Additional features
Operation temperature 
>0-40ºC / 32 to 104ºF
Relative Humidity 
90% RH maximum (non condensing)
Altitude without decreasing 
power 
2000 ASL (above sea level)
Acoustic level 
<50dBA
Dimensions (mm) 
440x88x680 
440x132x680
Weight  (kgs) 
24.0  - No batteries in UPS
26.0 - No batteries in UPS
207ENFW00