System Power-up   
▀  Verifying System Startup 
 
 
▄  ASR 5500 Installation Guide 
108 
   
Verifying System Startup 
When power is applied to the chassis, power is provided to the upper and lower fan trays, and every installed card.  
Light emitting diodes (LEDs) on all circuit cards and daughter cards indicate operating status. 
Important:
  As the system progresses through its boot process, LED activity will eventually occur on all cards. 
Allow several minutes to elapse prior to checking the status LEDs on the various cards.  
Checking PFU Status 
The blue LEDs above the circuit breakers on each PFU should all be ON.  
If all of the LEDs on a PFU are OFF, check the following: 
 
The PFU is firmly seated in the midplane connectors. 
 
All circuit breakers on the PFU are set to ON. 
 
All circuit breakers for power feeds from the local power distribution panel are ON. 
 
-48 VDC power is available from the PDF to the local PDP. 
If any LED is OFF, check the following: 
 
PFU circuit breaker is ON. 
 
Voltage is present at corresponding input terminal at rear of the PFU. 
 
Cable connection at PFU terminals is secure. 
 
Circuit breaker for the power feed from the local PDP is ON. 
 
Cable connection at the PDP terminal is secure. 
Checking Status LEDs on MIOs 
The table below identifies the operational and transitional states for LED indicators on an MIO /UMIO card. 
Table 16.  MIO/UMIO Operating States and Status LED Indicators 
Label
 
LED Color
 
LED State
 
Notes
 
Card Transition
 
Run/Fail
 
Green
 
Blink
 
Card is booting, starting or initializing.
 
Active
 
 
OFF
 
Redundant
 
 
OFF
 
Master
 
 
OFF
 
Busy
 
 
OFF