• 19-inch (482.6-mm) or 23-inch (584.2-mm) reversible (two-way) mounting brackets that can be rotated to fit either rack size.
These reversible brackets are used for EIA and IEC standard racks.
• ETSI brackets that are used for 600 mm x 600 mm or 600 mm x 300 mm ETSI racks.
The patch panel is shipped with the mounting brackets in the 19-inch (482.6-mm) position.
Note
The patch panel mounting brackets can be mounted such that the patch panels project:
• 4.2, 4.9, 7.6, or 9.2 inches from the front of the EIA standard racks fixing plane (or)
• 39 mm from the front of the ETSI standard racks fixing plane (or)
• 55 mm from the front of the IEC standard racks fixing plane
Diagram 1 in the following figure shows 4.2 inch recess location for EIA standard racks.
Diagram 2 in the following figure shows 4.9 inch recess location for EIA standard racks.
Figure 2: 19-inch Brackets with 4.2" and 4.9" Recess Location for EIA Standard Racks
Diagram 1 in the following figure shows 7.6 inch recess location for EIA standard racks.
Diagram 2 in the following figure shows 9.2 inch recess location for EIA standard racks.
Figure 3: 19-inch Brackets with 7.6" and 9.2" Recess Location for EIA Standard Racks