4-4        Automatically Configure a DeviceNet Network
Set the Address of a Scanner
ControlLogix Scanner 1756-DNB
DriveLogix and FlexLogix Scanner 1788-DNBO
DeviceNet
TM
MOD/NET   I/O          OK
1. Connect the device to the network. (If disconnected or the network power is off, the 
pushbutton changes the baud rate.)
2. Turn on the power to the device.
3. Press and hold the manual configuration pushbutton until the device displays the desired 
address.
When you release the button, the device resets to the new address.
4. After the device resets, check the 4-character display on the front of the module:
If:
Then the:
A#address
address is OK
Duplicate Node Address
address conflicts with another device
1. To change the address, press the button above or below a number.
2. Connect the device to the network.
3. Turn on power to the device.
4. Check the NS (network status) light.
If:
Then the:
green (flashing or solid)
address is OK
solid red
address and/or baud rate conflict with another device
31288-M